9 Specications
9.1 Electrical Data
Frequency converter
typical shaft output [kW]
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
Enclosure IP20 K1 K1 K1 K1 K1 K1 K2
Output current
Shaft output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3
Continuous (3x380–440 V) [A] 1.2 1.7 2.2 3 3.7 5.3 7.2
Continuous (3x441–480 V) [A] 1.1 1.6 2.1 2.8 3.4 4.8 6.3
Intermittent (60 s overload) [A] 1.9 2.7 3.5 4.8 5.9 8.5 11.5
Continuous kVA (400 V AC) [kVA] 0.84 1.18 1.53 2.08 2.57 3.68 4.99
Continuous kVA (480 V AC) [kVA] 0.9 1.3 1.7 2.5 2.8 4.0 5.2
Maximum input current
Continuous (3x380–440 V) [A] 1.2 1.6 2.1 2.6 3.5 4.7 6.3
Continuous (3x441–480 V) [A] 1.0 1.2 1.8 2.0 2.9 3.9 4.3
Intermittent (60 s overload) [A] 1.9 2.6 3.4 4.2 5.6 7.5 10.1
More specications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4(12)
Estimated power loss at rated maximum load
[W]
1)
20.88 25.16 30.01 40.01 52.91 73.97 94.81
Weight, enclosure IP20 2.3 2.3 2.3 2.3 2.3 2.5 3.6
Eciency [%]
2)
96.2 97.0 97.2 97.4 97.4 97.6 97.5
Table 9.1 Mains Supply 3x380–480 V AC
Frequency converter
typical shaft output [kW]
P4K0
4
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
IP20 K2 K2 K3 K4 K4 K5 K5
Output current
Shaft output 4 5.5 7.5 11 15 18.5 22
Continuous (3x380–440 V) [A] 9 12 15.5 23 31 37 42.5
Continuous (3x441–480 V) [A] 8.2 11 14 21 27 34 40
Intermittent (60 s overload) [A] 14.4 19.2 24.8 34.5 46.5 55.5 63.8
Continuous kVA (400 V AC) [kVA] 6.24 8.32 10.74 15.94 21.48 25.64 29.45
Continuous kVA (480 V AC) [kVA] 6.8 9.1 11.6 17.5 22.4 28.3 33.3
Maximum input current
Continuous (3x380–440 V) [A] 8.3 11.2 15.1 22.1 29.9 35.2 41.5
Continuous (3x441–480 V) [A] 6.8 9.4 12.6 18.4 24.7 29.3 34.6
Intermittent (60 s overload) [A] 13.3 17.9 24.2 33.2 44.9 52.8 62.3
More specications
Maximum cable size (mains, motor, brake)
[mm
2
(AWG)]
4(12) 16(6)
Estimated power loss at rated maximum load
[W]
1)
115.5 157.54 192.83 289.53 393.36 402.83 467.52
Weight enclosure IP20 [kg] 3.6 3.6 4.1 9.4 9.5 12.3 12.5
Eciency [%]
2)
97.6 97.7 98.0 97.8 97.8 98.1 97.9
Table 9.2 Mains Supply 3x380–480 V AC
1) The typical power loss is at nominal load conditions and expected to be within
±
15% (tolerance relates to variety in voltage and
cable conditions).
Specications Operating Instructions
MG07A102 Danfoss A/S © 11/2015 All rights reserved. 47
9 9