Symptom Possible cause Test Solution
Open power fuses
or circuit breaker
trip
Phase-to-phase short
Motor or panel has a short phase-to-
phase. Check motor and panel phase
for shorts.
Eliminate any shorts detected.
Motor overload
Motor is overloaded for the
application.
Perform the start-up test and verify
that motor current is within speci-
cations. If motor current is exceeding
nameplate full load current, the
motor may run only with reduced
load. Review the specications for the
application.
Loose connections
Perform pre-startup check for loose
connections.
Tighten loose connections.
Mains current
imbalance greater
than 3%
Problem with mains power (See
Alarm 4, Mains phase loss
description)
Rotate input power leads into the
frequency converter 1 position: A to B,
B to C, C to A.
If the imbalanced leg follows the
wire, it is a power problem. Check
mains supply.
Problem with the frequency
converter unit
Rotate input power leads into the
frequency converter 1 position: A to B,
B to C, C to A.
If the imbalanced leg stays on same
input terminal, it is a problem with
the unit. Contact the supplier.
Motor current
imbalance greater
than 3%
Problem with motor or motor wiring
Rotate output motor leads 1 position:
U to V, V to W, W to U.
If the imbalanced leg follows the
wire, the problem is in the motor or
motor wiring. Check motor and
motor wiring.
Problem with the frequency
converter unit
Rotate output motor leads 1 position:
U to V, V to W, W to U.
If the imbalanced leg stays on same
output terminal, it is a problem with
the unit. Contact the supplier.
Acoustic noise or
vibration (for
example a fan blade
is making noise or
vibrations at certain
frequencies)
Resonances, for example, in the
motor/fan system
Bypass critical frequencies by using
parameters in parameter group 4-6*
Speed Bypass.
Check if noise and/or vibration have
been reduced to an acceptable limit.
Turn o overmodulation in
parameter 14-03 Overmodulation.
Increase resonance damping in
parameter 1-64 Resonance Dampening.
Table 8.2 Troubleshooting
Maintenance, Diagnostics, a...
VLT
®
Midi Drive FC 280
46 Danfoss A/S © 11/2015 All rights reserved. MG07A102
88

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals