7 Application Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Required switch settings for analog terminals 53
or 54 are also shown.
NOTICE
When the STO feature is not used, a jumper wire is
required between terminals 12, 37, and 38 for the
frequency converter to operate with factory default
programming values.
7.1.1 AMA
Parameters
130BE203.11
FC
+24 V
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
12
13
18
19
27
29
32
33
50
53
54
55
42
A OUT
D IN
+24 V
Function Setting
Parameter 1-29 A
utomatic Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
Parameter 5-12 T
erminal 27
Digital Input
*[2] Coast
inverse
*=Default value
Notes/comments: Set
parameter group 1-2* Motor
Data according to motor
specications.
NOTICE
If terminal 12 and 27 are
not connected, set
parameter 5-12 Terminal 27
Digital Input to [0] No
operation.
Table 7.1 AMA with T27 Connected
7.1.2 Speed
Parameters
130BE204.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
0 ~10 V
+
-
FC
+24 V
Function Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50
Parameter 6-19 T
erminal 53 mode
[1] Voltage
*=Default value
Notes/comments:
Table 7.2 Analog Speed Reference (Voltage)
Parameters
130BE205.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
4 - 20mA
+
-
FC
+24 V
Function Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50
Parameter 6-19 T
erminal 53 mode
[0] current
*=Default value
Notes/comments:
Table 7.3 Analog Speed Reference (Current)
Application Examples
VLT
®
Midi Drive FC 280
38 Danfoss A/S © 11/2015 All rights reserved. MG07A102
77

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals