EasyManuals Logo
Home>Delta>Servo Drives>ASDA-A2 Series

Delta ASDA-A2 Series User Manual

Delta ASDA-A2 Series
721 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #150 background imageLoading...
Page #150 background image
ASDA-A2 Chapter 5 Trial operation and Tuning
Revision February, 2017 5-17
NOTE
1. Parameter P2-44 and P2-46 are the setting value of resonance suppression. If the value has been set
to the maximum (32dB), and still cannot suppress the resonance, please reduce the speed bandwidth.
After setting P2-47, users can check the value of P2-44 and P2-46. If the value of P2-44 is not 0, it
means the resonance frequency exists in the system. Then, users can access P2-43 to see the
resonance frequency (Hz). When there is another resonance frequency, the information will be shown in
P2-45 and p2-46.
2. If resonance still exists, repeatedly set P2-47 to 1 for 3 times and manually adjust the setting of
resonance.

Table of Contents

Other manuals for Delta ASDA-A2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-A2 Series and is the answer not in the manual?

Delta ASDA-A2 Series Specifications

General IconGeneral
BrandDelta
ModelASDA-A2 Series
CategoryServo Drives
LanguageEnglish

Related product manuals