Chapter 10 Troubleshooting ASDA-A2
Revision February, 2017 10-29
10.5 Corrective Actions after the Alarm Occurs
AL001
:Over current
Turn DI.ARST on to clear the alarm
AL002
:Over voltage
Turn DI.ARST on to clear the alarm
AL003
:Undervoltage
The alarm can be cleared after the
voltage returns to normal.
AL004
:The magnetic field of the motor is abnormal
The alarm can be cleared after re-
power on.
AL005
:Regeneration error
Turn DI.ARST on to clear the alarm
AL006
:Overload
Turn DI.ARST on to clear the alarm
AL007
:Excessive speed deviation
Turn DI.ARST on to clear the alarm
AL008
:Abnormal pulse command
Turn DI.ARST on to clear the alarm
AL009
:Excessive deviation of position control
Turn DI.ARST on to clear the alarm
AL011
:Encoder error
The alarm can be cleared after re-
power on.
AL012
:Adjustment error
The alarm can be cleared when
removing CN1 wiring and execute
auto adjustment.
AL013
:Emergency stop
The alarm can be cleared
automatically after turning DI.EMGS
off
AL014
:Reverse limit error
Turn DI.ARST on or Servo Off to clear
the alarm. The alarm also can be
cleared when the motor operates
backwards.
AL015
:Forward limit error
Turn DI.ARST on or Servo Off to clear
the alarm. The alarm also can be
cleared when the motor operates
backwards.
AL016
:The temperature of IGBT is abnormal
Turn DI.ARST on to clear the alarm
AL017
:Abnormal EEPROM
If the alarm occurs, then parameter
reset is a must. And re-servo on
again. If it happens during the
operation, please turn DI.ARST on to
clear the alarm.
AL018
:Abnormal signal output
Turn DI.ARST on to clear the alarm
AL019
:Serial communication error
Turn DI.ARST on to clear the alarm
AL020
:Serial communication timeout
Turn DI.ARST on to clear the alarm
AL022
:Main circuit power leak phase
Turn DI.ARST on to clear the alarm

Table of Contents

Other manuals for Delta ASDA-A2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-A2 Series and is the answer not in the manual?

Delta ASDA-A2 Series Specifications

General IconGeneral
BrandDelta
ModelASDA-A2 Series
CategoryServo Drives
LanguageEnglish

Related product manuals