5.2.8.6. Constant Q
此模式啟動後,逆變器可饋入固定比例之虛功功率至市電,使用者可透過
設定頁面指定欲饋入之虛功功率量。
5.2.8.7. Q(V)
此模式啟動後,逆變器會隨著市電電壓變化而饋入不同性質的虛功功率。
當國家設定為Italy LV或Italy MV時,使用者可進一步指定輸出功率達到
P lock-in時方饋入虛功,輸入功率小於P lock-out時則無論市電電壓為何,
皆不饋入任何虛功。
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
Mode
Fix Q
OFF
Ind 90%
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
EXIT
EXIT
Mode
V1s
V2s
Qs limit
OFF
248.4V
253.0V
Ind 44%
V1i
V2i
Qi limit
T delay
211.6V
207.0V
Cap 44%
10.00s
P lock-in
P lock-out
20%
5%
204