V
1s
V
2s
V
1i
V
2i
Q
i limit
Q
s limit
V
Q
V
1s
V
2s
V
1i
V
2i
Q
i limit
Q
s limit
V
Q
Curve A Curve B
Others Italy MV & Italy LV
圖 5-28 Q(V)參數對照
圖5-29 FRT頁面
圖5-30 FRT參數對照
5.2.9. FRT (Fault ride through)
根據某些特定地區之電力法規規範,當市電電壓發生驟降時,在一定的時間
內逆變器必須維持併網狀態。使用者可透過啟動FRT功能並設定所需的參數
來達到這項要求。
100%
U1
0
t1
Fault occurence
t3
time
U
grid/
U
nom
Umin
Udrop
Disconnect from grid
Stay connected
General Settings
Install Settings
Active/Reactive Pwr
FRT
ENT
EXIT
ENT
EXIT
EXIT
Mode
Dead Band
Vdrop
t1
OFF
-10%
0%
0.30s
U1
t3
K factor
20%
3.00s
2.0
Warning:
Adj. would affect
energy production.
Password:
****
205