EasyManuals Logo
Home>Delta>Inverter>RPI M30A

Delta RPI M30A User Manual

Delta RPI M30A
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
5.2.7.6. EPO
EPO function has 2 detection methods: Normal Open and Normal Close.
Normal Open means EPO pins are usually open-circuited. When these
two pins are short-circuited, inverter will shut down immediately.
Normal Close is contrary to Normal Open. Please choose an appropriate
detection method according to your needs.
5.2.7.7. AC connection
RPI M30A and M50A models can support 3P3W and 3P4W system.
Please select the correct AC wiring type.
5.2.7.8. Max. Power
Electricity regulation in some area requests that inverter must have power
limit function. In these areas, users can adjust Max. Power to limit the
maximum output power of the inverter.
DC Injection
Dry Contact
RCMU
EPO
ON
Normal Close
Figure 5-15 EPO page
Figure 5-16 EPO page
Figure 5-17 Max. Power page
AC Connection
Anti-islanding
Max. Power
Return to Factory
3P4W
ON
52500W
AC Connection
Anti-islanding
Max. Power
Return to Factory
3P4W
ON
52500W
49
Turn on PV inverter

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M30A and is the answer not in the manual?

Delta RPI M30A Specifications

General IconGeneral
BrandDelta
ModelRPI M30A
CategoryInverter
LanguageEnglish

Related product manuals