Chapter 12 Description of Parameter SettingsME300
12.1-02-10
The default for bit 0 (MI1) is FWD terminal, and the default for bit 1 (MI2) is REV terminal. You
cannot use this parameter to change the input mode when Pr.02-00 ≠ 0.
You can change the terminal ON / OFF status through communications.
For example: MI3 is set to 1 (multi-step speed command 1) and MI4 is set to 2 (multi-step speed
command 2). Then the forward + second step speed command = 1001
2
= 9
10
.
As long as Pr.02-12 = 9 is set through communications, there is no need to wire any multi-function
terminal to run forward with the second step speed.
bit 4 bit 3 bit 2 bit 1 bit 0
MI5 MI4 MI3 MI2 MI1
Use Pr.11-42 bit 1 to select whether the FWD / REV terminal is controlled by Pr.02-12 bit 0 and
bit 1.
Multi-function Output 1 (Relay1)
Default: 11
Multi-function Output 2 (MO1)
Default: 0
Settings 0: No function
1: Indication during RUN
2: Operation speed reached
3: Desired frequency reached 1 (Pr.02-22)
4: Desired frequency reached 2 (Pr.02-24)
5: Zero speed (Frequency command)
6: Zero speed, includes STOP (Frequency command)
7: Over-torque 1 (Pr.06-06–06-08)
8: Over-torque 2 (Pr.06-09–06-11)
9: Drive is ready
10: Low voltage warning (LV) (Pr.06-00)
11: Malfunction indication
13: Over-heat warning (Pr.06-15)
14: Software brake signal indication (Pr.07-00)
15: PID feedback error
16: Slip error (oSL)
17: Count value reached (Pr.02-20; does not return to 0)
18: Count value reached (Pr.02-19; returns to 0)
19: External interrupt B.B. input
(Base Block)
20: Warning output
21: Over-voltage
22: Over-current stall prevention
23: Over-voltage stall prevention
24: Operation source
25: Forward command
26: Reverse command