EasyManuals Logo
Home>Delta>DC Drives>VFD4A2ME43ANNAA

Delta VFD4A2ME43ANNAA User Manual

Delta VFD4A2ME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #265 background imageLoading...
Page #265 background image
Chapter 12 Description of Parameter SettingsME300
12.1-06-6
Over-torque Detection Level (Motor 2)
Default: 120
Settings 10–250% (100% corresponds to the rated current of the drive)
Over-torque Detection Time (Motor 2)
Default: 0.1
Settings 0.0–60.0 sec.
When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and also
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows
the setting of Pr.06-06 and Pr.06-09.
When you set Pr.06-06 or Pr.06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running. The warning remains on until the output current is smaller than 5% of the over-torque
detection level.
When you set Pr.06-06 or Pr.06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops
running after over-torque detection. The drive keeps running after you manually reset it.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A2ME43ANNAA and is the answer not in the manual?

Delta VFD4A2ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A2ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals