EasyManuals Logo
Home>Delta>DC Drives>VFD4A2ME43ANNAA

Delta VFD4A2ME43ANNAA User Manual

Delta VFD4A2ME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #249 background imageLoading...
Page #249 background image
Chapter 12 Description of Parameter SettingsME300
12.1-03-16
AVI Terminal Input Selection
Default: 0
Settings
0: 0–10 V
1: 0–20 mA (Pr.03-57–03-62 is valid)
2: 4–20 mA (Pr.03-57–03-62 is valid)
Switch between voltage mode and current mode must work with manual switch. Refer to Chapter
06 for more information on AVI terminals.
AFM DC Output Setting Level
Default: 0.00
Settings
0.00–100.00%
AFM Filter Output Time
Default: 0.01
Settings
0.00–20.00 sec.
VR Input Selection
Default: 1
Settings 0: Disable
1: Frequency command
VR Input Bias
Default: 0.0
Settings
-100.0–100.0%
VR Positive / Negative Bias
Default: 0
Settings
0: No bias
1: Lower than or equal to
bias
2: Greater than or equal to bias
3:
The absolute value of the bias voltage while serving as the center
4: Bias serves as the center
VR Gain
Default: 100.0
Settings
-500.0–500.0%
VR Filter Time
Default: 0.01
Settings 0–2.00 sec.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A2ME43ANNAA and is the answer not in the manual?

Delta VFD4A2ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A2ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals