3.2.3 UPS System Interface Wiring Preparation
Control wiring for features and options should be connected at the customer interface terminal blocks located
on top front of the UPS, behind the door.
DANGER
Donotdirectlyconnectrelaycontactstothemainsrelatedcircuits.Reinforcedinsulationtothemainsisrequired.
Read and understand the following notes while planning and performing the installation:
• Allinterfacewiringistobeprovidedbythecustomer.
• WheninstallinginternalinterfacewiringtoMini-slotterminals,routethewiringthroughtheinternal
opening in the Mini-slot communication bay.
• Allsignalinputsorremotefeaturesrequireanisolatednormally-opencontactorswitch(ratedat24
VDC, 20 mA minimum) connected between the alarm input and common terminal. All control wiring
and relay and switch contacts are customer-supplied. Use twisted-pair wires for each alarm input and
common.
• Thesignalinputscanbeprogrammedtodisplaythealarmfunctionalname.
• LANandtelephonedropsforusewithMini-slotcardsmustbeprovidedbyfacilityplannersorthe
customer.
• TheUPSBatteryAuxand24VDCShuntTripsignalwiringfromtheUPStotheDCsourcedisconnect
device is optional.
• BatteryAuxand24VDCShuntTripwiringshouldbeaminimumof1.5mm².
• TheRemoteEPOfeatureopensallswitchgearintheUPScabinetandisolatespowerfromyourcriti-
cal load. Local electrical codes may also require tripping upstream protective devices to the UPS.
• TheRemoteEPOswitchmustbeadedicatedswitchnottiedtoanyothercircuits.
• Ajumperwiremustbeconnectedbetweenpins1and2onconnectorEPO,ifthenormallyclosed
(NC) remote EPO contact is used.
• RemoteEPOwiringshouldbeaminimumof0.75mm²andamaximumof2.5mm².
• ThemaximumdistancebetweentheRemoteEPOandtheUPScannotexceed150meters.
• Alarmrelaycontactshaveamaximumcurrentratingof5Aandaswitchedvoltageratingof30VAC
(RMS) and 30 VDC.
• Alarmrelaywiringshouldbeaminimumof0.75mm².

Table of Contents

Other manuals for Eaton 93PR Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 93PR Series and is the answer not in the manual?

Eaton 93PR Series Specifications

General IconGeneral
BrandEaton
Model93PR Series
CategoryUPS
LanguageEnglish

Related product manuals