25-75 kW
User's and Installation Guide
81
8.3 UPS System Output
Table 8-3: UPS System Output
Number of Output Phases
Rated Output Voltage
3 phases + N
220/380 V; 230/400 V; 240/415 V, configurable
Total Voltage Harmonic Distortion
100%LinearLoad
100%Non-LinearLoad
< 1 %
< 5 %
RatedOutputFrequency
OutputFrequencyVariation
SlewRate
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
Overload Capability at Ambient 40 °C
(onInverter)
10 min 105-110 % load
60 sec 111-125 % load
10 sec 126-150 % load
300 ms > 150 % load
Overload Capability at Ambient 40 °C
(onInverter,StoredEnergyMode)
10 min 105-110 % load
60 sec 111-125 % load
300 ms > 126 % load
Overload Capability at Ambient 40 °C
(onBypass)
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
Output Current
See Table 3-7: Rated and maximum currents for rated
power and voltage on page 31
LoadPowerFactor,(Rated)
1. 0
LoadPowerFactor,(PermittedRange)
From 0.8 lagging to 0.8 leading