Product Specifications
9-2 Eaton 9E UPS (40–60 kVA, 208/220V) Installation and Operation Manual P-164000058—Rev 4 www.eaton.com/powerquality
9.2.2 UPS Output
9.2.3 UPS Environmental
9.2.4 Battery Runtimes (in Minutes) at Full load
UPS Output Capacity 100% rated current
Output Voltage Regulation ± 1% (10% to 100% load)
Nominal Output Voltage 208 Vac and 220 Vac nominal
Output Voltage Harmonic Content 2% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current See Table 3-4.
Output Voltage Balance < 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
< 2.5 for 100% maximum load imbalance (linear load)
Frequency Regulation 0.1 Hz free running
Synchronous to Bypass ± 4 Hz (default setting)
Frequency Slew Rate 3 Hz per second (default setting)
Load Compatibility 0.8 pF Leading
0.8 pF Lagging
Overload Capability <110% for 10 minutes
<125% for 30 seconds
<150% for 150 milliseconds
>150% for 40 milliseconds
Operating Temperature 0 to 30C (32 to 86F) without derating. The recommended operating
temperature is 25C(77F).
Operating Altitude Maximum 1500m (5000 ft) at 30C without derating
Storage Temperature 25 to +55C, excluding batteries (prolonged storage above 40C causes
rapid battery self-discharge)
Relative Humidity (operating and
storage)
5% to 95% maximum noncondensing
Acoustical Noise Less than or equal to 65 dB at a 1m distance, per ISO 7779
EMI Emissions and Immunity Meets IEC 62040-2 C3 and FCC Part 15 Subpart B, ICES-003, CISPR 22,
CISPR 24, and VCCI: Class A
Electrostatic Discharge (ESD)
Immunity
Meets IEC 61000-4-5 Level 4 specifications. Withstands up to 4 kV pulse
without damage and with no disturbance or adverse effect to the critical
load.
UPS Model Number of Battery Strings Runtime
9E-40 6 7
9E–60/40 8 12
9E–60/60 8 6.6
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.