UPS System Installation
Eaton 9E UPS (40–60 kVA, 208/220V) Installation and Operation Manual P-164000058—Rev 4 www.eaton.com/powerquality 4-19
k. Install the power terminal cover right and left sides using the provided hardware.
4. Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure
Figure 4-11 and Figure 4-17 for wiring information.
5. Route and install pull chain wiring between the UPS cabinets and cabinet MOBs. See Figure 4-11,
Figure 4-16, and Figure 4-17 for wiring information.
6. Reinstall the interface terminal cover using the retained hardware.
7. If wiring Mini-Slot connections, proceed to paragraph 4.11.3; otherwise, proceed to Step 8.
8. Install the power terminal cover top using the provided hardware (see Figure 4-9).
9. Install the power terminal cover right and left sides using the provided hardware.
10. Proceed to paragraph 4.13.
4.11.3 Installing Mini-Slot Interface Connections
For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8)
To install wiring:
1. If not already installed, install the LAN drop.
2. Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-10 and
Figure 4-11 for Mini-Slot communication bay locations.
3. Refer to the manual supplied with the Mini-Slot card for operator instructions.
4. Install the power terminal cover top using the provided hardware (see Figure 4-9).
5. Install the power terminal cover right and left sides using the provided hardware.
6. Proceed to paragraph 4.13.
NOTE LAN drop for use with Mini-Slot cards must be provided by the customer.