42 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 10. Electrical Input
Model Default Input
(Voltage/Max Current)
Input Nominal Voltages Input Voltage Window at Rated
Load
9PX1500IRT2U-L 230V / 10A 200V, 208V, 220V, 230V,
240V
at 100% load: 176-276V
at <33% load: 100-276V
9PX1500IRT2U-L 230V / 10A 200V, 208V, 220V, 230V,
240V
at 100% load: 176-276V
at <33% load: 100-276V
9PX2200IRT2U-L 230V / 10A 200V, 208V, 220V, 230V,
240V
at 100% load: 176-276V
at <33% load: 100-276V
9PX3000IRT2U-L 230V / 16A 200V, 208V, 220V, 230V,
240V
at 100% load: 176-276V
at <33% load: 100-276V
Nominal Frequency 50/60Hz auto-sensing
Frequency Range 40-70Hz before transfer to battery
Bypass Voltage Range
-20% / +15% of nominal value (default)
Noise Filtering Input EMC filter
Table 11. Electrical Input Connections
Model Input Connection Input cable
9PX1500IRT2U-L IEC-C14 IEC10A ( Not Included)
9PX2200IRT2U-L IEC-C20 IEC16A
9PX3000IRT2U-L IEC-C20 IEC16A
Table 12. Electrical Output
All Models Normal Mode Efficiency Mode Battery Mode
Voltage Regulation ±1% ±2%
Efficiency
91% for 1.5K
93.5% for 2K
94% for 3K
96.5% for 1.5K
98% for 2K
98% for 3K
89% for 1.5K
90% fo r 2K
90% for 3K
Frequency Regulation
Sync with line ±5% of nominal line frequency (outside this
range: ±0.5% of auto-selected nominal frequency)
±0.5% of auto-selected
nominal frequency
Nominal Output
[200V] [208V] [220V] [230V] [240V] (Voltage configurable)
Frequency 50 or 60 Hz, autosensing or configurable as a frequency converter
Output Overload
Online mode:
102%~130% :12s
130%~150% :2s
>150% :shutdown after 300ms
Percent is based on nominal Watt/VA.
Transfer behavior can change (see output mode setting)
Battery mode:
102%~130% :12s
Model Specifications