2.2.11 Internal Audible Alarm
An integrally mounted 2.4Khz speaker is located on the common services card.
To adjust to volume use the slider in the SmartAlarm congurator as shown below.
2.2.12 HNA & HNB Horn Relays
Common Relay – HNA & HNB are used as Horn Relays and the following options are
software selectable:-
• Any channel within the annunciator can be set to operate either relay as required.
• The relay coil state can be set to Normally Energised or Normally De-Energised.
• The relay can be disabled to prevent it operating on System Test.
• The relay can be disabled to prevent it operating during Sleep Mode.
• Relay mode is set to horn as default but can be modied to other modes using the
conguration software.
2.2.13 GPA & GPB Common Alarm Group Relays
Common Relay – GPA & GPB are used as Group Relays and the following options are
software selectable:-
• Any channel within the annunciator can be set to a common alarm group.
• The group function can be set to “alarm” which keeps the signal active until the
alarm has been cleared.
• Any “alarm” group within the annunciator can be linked to either relay as required.
• A reash function can be selected per group which allows the contacts to revert
to normal and re-alarm each time a new alarm occurs within the same group. The
reash pulse duration can be set between 1mS and 65,000mS.
• The relay state can be set to Normally Open or Normally Closed.
• The relay can be disabled to prevent it operating on System Test.
• The relay can be disabled to prevent it operating during Sleep Mode.
• Relay mode is set to group as default but can be modied to other modes using
the conguration software.