Please Note:-
The drop down menu within the conguration software allows the user to select ISA Sequence
A-4-5-6 to obtain Status Only indication.
If the audible alarm sounds on a channel that has been set to Status only please check that the
channel is not part of a “Group” which has been assigned to operate as an “Audible” under the
group operations tab.
In the example below Group 8 is being used as an audible group.
30.9.1 Group Tab
This screen shot indicates that a channel has been set to Group 8.
30.9.2 Group Operations Tab
This screen shot indicates that Group “Type” for Group 8 has been set to operate as “Audible”.
To prevent the audible sounding the user should select the associated alarm LED on the software
faceplate and uncheck the tick box associated with any Group being used as an Audible in the
example above this would be Group 8.