EasyManuals Logo
Home>Eaton>Lighting Equipment>Crouse-hinds series

Eaton Crouse-hinds series User Manual

Eaton Crouse-hinds series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
77
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
Please Note:-
The drop down menu within the conguration software allows the user to select ISA Sequence
A-4-5-6 to obtain Status Only indication.
If the audible alarm sounds on a channel that has been set to Status only please check that the
channel is not part of a “Group” which has been assigned to operate as an Audible” under the
group operations tab.
In the example below Group 8 is being used as an audible group.
30.9.1 Group Tab
This screen shot indicates that a channel has been set to Group 8.
30.9.2 Group Operations Tab
This screen shot indicates that Group “Type” for Group 8 has been set to operate as Audible.
To prevent the audible sounding the user should select the associated alarm LED on the software
faceplate and uncheck the tick box associated with any Group being used as an Audible in the
example above this would be Group 8.

Table of Contents

Other manuals for Eaton Crouse-hinds series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Crouse-hinds series and is the answer not in the manual?

Eaton Crouse-hinds series Specifications

General IconGeneral
BrandEaton
ModelCrouse-hinds series
CategoryLighting Equipment
LanguageEnglish

Related product manuals