46
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
17.16 Reash Pulse Length
As indicated above the group relays can have a reash feature enabled which interrupts the output
each time a new alarm occurs within the group. The reash pulse length can be set in tenths of a
second to suit individual applications.
17.17 Alternative Functions for any Relay
The drop-down menu provided next to the Assignment Field” of each relay allows the user to set
any of the Relays to:-
Any group (Group-1 to Group-30).
Any group with Reash enabled (Group-1 to Group-30).
Pushbutton Follower where the relay will faithfully follow the operation of any one of the
following Pushbutton functions:- Lamp Test, Mute, Ack, Reset, 1st Reset or System Test.
All faults Relay where the relay activates if any fault is detected within the Annunciator.
Field Contact fault where the relay activates when the signal supply is lost which can be
used to ag 3rd Party devices.

Table of Contents

Other manuals for Eaton Crouse-hinds series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Crouse-hinds series and is the answer not in the manual?

Eaton Crouse-hinds series Specifications

General IconGeneral
BrandEaton
ModelCrouse-hinds series
CategoryLighting Equipment
LanguageEnglish

Related product manuals