EasyManuals Logo
Home>Eaton>Lighting Equipment>Crouse-hinds series

Eaton Crouse-hinds series User Manual

Eaton Crouse-hinds series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #92 background imageLoading...
Page #92 background image
84
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
SEQUENCE FEATURES
1. Silence, acknowledge, reset and test pushbuttons
2. Alarm audible device
3. Lock-in of momentary alarms until acknowledged.
4. Option1 – silence pushbutton to silence the alarm audible device while retaining the rst out
ashing indication
5. Flashing indication for rst alarm only. new subsequent alarms have the same visual
indication as acknowledged alarms.
6. First out indication is reset when acknowledged
7. Manual reset of acknowledged alarm indications after process conditions return to normal.
8. Operational test
30.17 ISA F2A-1 – Automatic Reset First Up
This sequence is the same as ISA F2M-1 with the exception that the alarms are automatically reset
once the process has returned to normal.
30.18 ISA F3A – Automatic Reset First Up

Table of Contents

Other manuals for Eaton Crouse-hinds series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Crouse-hinds series and is the answer not in the manual?

Eaton Crouse-hinds series Specifications

General IconGeneral
BrandEaton
ModelCrouse-hinds series
CategoryLighting Equipment
LanguageEnglish

Related product manuals