52 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
[91]
Display: 91
[ENTER]
BatAmpHrs: 0 AH
[PROGRAM] 91 Pgm: (Enter in Amp hour of the battery you are using)
NOTE ABM provides optimum battery performance and lifetime improving total cost of
ownership. ABM will be enabled when the total UPS and EBM battery capacity is less
than or equal to 200Ah. ABM is disabled for UPS and EBM battery capacity exceeding
200 Ah and the UPS internal charger will switch to float charge mode.
88..44 AAuuttoommaattiicc BBaatttteerryy TTeesstt
The Eaton FX Ferrups UPS has a built in automatic battery discharge test feature. When ABM is enabled (by
default) the battery discharge test will run automatically every 90 days. The duration of the battery test can be
modified by changing parameter 93.
93 AbmTestIntrvl 93 AbmIntrvl 3 mo User
3,4,5,6 Months
ABM Discharge Test
Interval.
If custom battery is enabled the battery test will run based on the custom battery test parameter set points
listed below.
72 TestIntrl 72 TestIntrl 7 d User 7 - 180
When using custom batteries, the
discharge test interval, the time
between discharge tests.
73 BatTestToD 73 Test@ 1:00:00 User 0 - 23:59:00
When using custom batteries, the
time of day that the battery discharge
test will start.
75 BatTestLen 75 BT Time 60 s User 60 - 180
When using custom batteries, the
test will discharge the batteries for
this amount of time.
Automatic Battery Test