31
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
11 INSTALLATION
11.1 Unpacking
Once the item has been unpacked please visually examine the unit for any signs of transit damage
before installing the unit into the control system. If any damage has occurred, please report the
damage to the freight forwarder and copy Eaton. The alarm annunciator is supplied with panel
mounting clamps locked in place, however please check all packages to ensure that no additional
pieces are left in the box as any auxiliary items like horns, pushbuttons or spares kits will be
packed separately.
Please double check that all items listed on the packing list have been unpacked before disposing
of any packing material.
11.2 Mounting
SmartAlarm annunciators are designed for panel mounting and therefore a suitable cut-out must
be provided to securely locate them using the Eaton panel mounting clamps provided on either
side of the annunciator. Each clamp can be tightened using a Philips screwdriver.
Dimensions for panel mounting versions
8 Way
• Overall:- 96mm H x 96mm W x 125mm D
• Cut-Out :- 91 + 0.5mm H x 91 +0.5mm W
16 Way
• Overall:- 96mm H x 144mm W x 125mm D
• Cut-Out:- 91 + 0.5mm H x 139 + 0.5mm W
24 Way
• Overall:- 96mm H x 192mm W x 125mm D
• Cut-Out:- 91 + 0.5mm H x 187 + 0.5mm W
• Maximum radius cut-out 3mm
32 Way
• Overall:- 96mm H x 240mm W x 125mm D
• Cut-Out:- 91 + 0.5mm H x 235.5 + 0.5mm W
• Maximum radius cut-out 3mm