25.3 Abnormal Delay (mS)
This option prevents the alarm occurring before a pre-set time period has elapsed. If an alarm
occurs the timer will automatically start and the alarm will occur as soon as the delay period has
passed.
25.4 Normal Delay (mS)
This option prevents the alarm returning to normal until the pre-set delay period has elapsed.
The default setting for the activation and deactivation is 10mS but can be selected between 1 and
65,000mS as required.
25.5 Remote
This eld is used to congure each input as hardwire (Normally Open / Normally Closed) or Serial
Input (Remote).
If the “Remote” check-box is enabled the input will activate via Serial Communications.
If the “Remote” check-box is unchecked the input will activate via a conventional hardwired
contact input (N/O or N/C).
To implement changes the user must select the “Conrm” icon and download the
conguration to the SmartAlarm using the “Tools” menu – “Send Settings” as required