Power Xpert SPD Modbus register map (cont.)
Register Name Attributes Description
12267 General log Index UINT16 RO Index points to the latest general event log
Default: 0
Range: 0 to 250
12268 Clear General Log Events BOOL RW NV Clear general event logs 1. Default value is zero 2. Writing 1 to the register will clear
the general logs.
Default: 0
Range: 0 to 1
12269 Phase A Total Surge Counts UINT32 RO Sum of phase A high, medium and low surge counts
Default: 0
Range: 0 to 999999
12271 Phase B Total Surge Counts UINT32 RO Sum of phase B high, medium and low surge counts
Default: 0
Range: 0 to 999999
12273 Phase C Total Surge Counts UINT32 RO Sum of phase C high, medium and low surge counts
Default: 0
Range: 0 to 999999
12275 DCI for Testing Display BOOL RW DCI test display, LED and alarm. Setting the value starts the display test, once the display
test is complete the value will be updated to zero by the firmware
Default: 0
Range: 0 to 1
12276 Ethernet MAC Address UINT8 RO NV Unique MAC address assigned to this device.(MAE)
Array size: 6 Array of 3 registers
MAC_ADDRESS()
Appendix G
Web user error codes
Error Message Description Action Required
Login Failed (Login Page) User not authorized to access device Contact administrator for authorization
One Admin Role is mandatory in System
User Self-Deletion Not Permitted Contact administrator to delete user
Username Already Exists Username already exists on the device Create unique username
User Database Full
Password Security Violation
Password Matches With Name or Existing Password Username and password match Create unique username and password
New password cannot match old password
User Locked Temporarily Too many users trying to access device
HTTP Version Not Supported
Failed to Fetch Device communication failed (login page), device communi-
cation failure (firmware update page)
Codepack integrity check has failed Image in the codepack file is corrupt Re-install firmware
Codepack integrity check has aborted firmware update Displayed when any one image is corrupt during multiple
firmware update
Re-install firmware
Final integrity check is invalid Multiple reasons