BLUEHELIX MAXIMA
203EN
cod. 3541U630 - Rev. 00 - 07/2020
2.7 Condensate drain connection
IMPORTANT
The boiler has an internal trap for draining condensate. Install the hose “B” by pressing it into place. Before commis-
sioning, fill the trap with approx. 0.5 L of water and connect the hose to the disposal system.
Drains connected to the drainage system must be resistant to acidic condensate.
If the condensate drain is not connected to the waste water drainage system, a neutralizer must be installed.
B
ATTENTION: THE UNIT MUST NEVER BE OPERATED WITH THE TRAP
EMPTY!
OTHERWISE THERE IS A DANGER OF SUFFOCATION DUE TO THE EMIS-
SION OF COMBUSTION FUMES.
THE CONDENSATE DRAIN MUST BE CONNECTED TO THE DRAINAGE SYS-
TEM IN SUCH A WAY THAT THE LIQUID CONTAINED CANNOT FREEZE.
fig. 23- Condensate drain connection
0,5lt
B