B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-1
B90 Low Impedance Bus Differential System
Chapter 5: Settings
Settings
This chapter outlines front panel and/or software settings. The relay is not taken out of service when saving settings; the
relay is taken out of service when a settings file is written to it. Settings can be viewed remotely in a web browser by
entering the IP address of the relay, accessing the Device Information Menu option, then the Front-Panel Display Report
option.
When indicated that a restart is required for a setting change to take effect, use the Maintenance > Reboot Relay
Command in the software.
5.1 Settings menu
 SETTINGS
 PRODUCT SETUP
B90 FUNCTION
See page 5-5

SECURITY
See page 5-5
DISPLAY
PROPERTIES
See page 5-23
GRAPHICAL FRONT PANEL Access in EnerVista
See page 5-24
CLEAR RELAY
RECORDS
See page 5-36
COMMUNICATIONS
See page 5-37
MODBUS USER MAP
See page 5-99
REAL TIME
CLOCK
See page 5-99
USER-PROGRAMMABLE
FAULT REPORT
See page 5-104
OSCILLOGRAPHY
See page 5-105