CHAPTER 6: ACTUAL VALUES STATUS
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-5
6
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.3.7 RxGOOSE status
ACTUAL VALUES STATUS  RxGOOSE STATUS
The
All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.
6.3.8 RxGOOSE statistics
ACTUAL VALUES STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
IGMP — Multicast (SSM and ASM) modes of R-GOOSE reception require that the B90 device subscribe to a multicast group
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.
RxGOOSE
STATUS
All RxGOOSE Online:
Yes
Range: Yes, No
RxGOOSE 1 Status:
Offline
Range: Online, Offline
RxGOOSE 64 Status:
Offline
Range: Online, Offline
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
RxGOOSE 1
RxGOOSE 1
stNum: 0
Range: 0 up to 4,294,967,295
RxGOOSE 1
sqNum: 0
Range: 0 up to 4,294,967,295
R-RxGOOSE 1
IGMP: Off
Range: On, Off
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.