EasyManua.ls Logo

GE Kelman TRANSFIX 1.6 - 8.3.2 Fitting Instructions; 8.3.3 Oil Supply Valve Connection

GE Kelman TRANSFIX 1.6
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MA-001 TRANSFIX-family Installation Manual Rev 3.0 18-Jan-16 Page 22 of 55
8.3.2 Fitting Instructions
1. Insert one end of the tubing into the Swagelok or Ham-Let fitting body as shown
in Figure 87.
Figure 87: Fitting body and tubing
2. Ensure that the tubing rests firmly on the shoulder of the fitting body and that the
nut is finger-tight.
3. Mark the nut with a fine-tipped permanent marker at the 6 o’clock position as
shown in Figure 88.
Figure 88: Nut at 6 o'clock position
4. While holding the fitting body steady, tighten the nut 1 and a 1/4 turns to the 9
o’clock position as shown in Figure 89.
Figure 89: Nut at 9 o'clock position
Do not use any type of thread sealant on compression-type tube fittings.
Do not open the valves on the transformer or the stainless steel tubing. This is
performed by GE-trained and certified personnel during the commissioning
phase to prevent air bubbles from entering the transformer.
8.3.3 Connection to Oil Supply Valve
Oil is typically taken from a valve midway up on the transformer or from an active cooling
loop (see Section 8.1 for information on valve selection). Oil must be taken from a location
where the oil is well mixed and in the active flow of the transformer oil. The temperature
of the oil at this location should not exceed 120 °C or be lower than 20 °C. Note: The
distance from the oil return valve should be at least 30 cm (12 in.).
These points must be observed when connecting to the oil supply valve:
Locate the valve on the transformer chosen for the oil supply line. Identify the
items needed to adapt the oil supply valve to a ¼ in. female NPT fitting. Select
fittings and adaptors made from stainless steel, brass or black iron.

Table of Contents

Related product manuals