6 3 SERIES RETROFIT – INSTRUCTION MANUAL
MIV AND MIV II RELAYS CHAPTER 1: OVERVIEW
The following table describes MIV II options, and the equivalent 350 options and order
codes. In some cases the 350 options have changed from those available for MIV II relays,
so read the descriptions carefully.
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
Feature MIV order code options MIV II order code options 350 order code options
Function MIV-1-000E000F00C
1: Voltage Functions
2: Frequency Functions
3: Voltage and Frequency Function
MIVII-1-010E00HI00
1: Voltage Functions
2: Frequency Functions
3: Voltage and Frequency Function
350E-PXGX-HE-N-N-V-SNNN
V: Voltage Metering - 27P(4), 27X(1),
27P_1(1), 59P(4), 59N(4), 59X(1),
59_2(2), 81O(4), 81U(4), 25(1), VTFF(1)
Voltage Range MIV10-0-0E000F00C
0: 10 - 250 V Setting Range
1: 2 - 60 V Setting Range
MIVII10-1-0E00HI00
0: 10 - 250 V Setting Range
1: 2 - 60 V Setting Range
All 350 models with the VT module:
Primary VT range: 0.15 to 550kV
VT Secondary range: 50 to 220V
Language All MIV relays come with English
standard.
MIVII1010-E-00HI00
E: English
F: French
T: Turkish
All 350 relays come with English
standard.
Power Supply MIV1000E000-F-00C
H:
110 - 250 VDC (Range: 88~300 VDC)
110 - 230 VAC (Range: 88~264 VAC)
F: 24 - 48 VDC (Range: 19~58 VDC)
MIVII1010E00-HI-00
HI:
110 - 250 VDC (Range: 88~300 VDC)
110 - 230 VAC (Range: 88~264 VAC)
LO: 28 - 48 VDC (Range: 19~58 VDC)
350EPXGX-H-ENNVSNNN
H: 110 - 250 VDC
110 - 230 VAC
L: 28 - 48 VDC
Environmental
Option
n/a MIVII1010E00HI-00
00: None
0H: Conformal Coating
350EPXGXHENNVSNN-N
N: None
H: Harsh Environment Conformal
Coating