44
UNDERWRITERS LABORATORIES INFORMATION
The NetworX NX-6 holds the following listings from Underwriters Laboratories (North America & Canada):
Household Burglary (UL1023) (ORD-C1023-1974)
Household Fire (UL985) (CAN/ULC-S545-M89)
Local Grade A Mercantile, Police Station Connect w/Basic Line Security (UL609) (requires NX-003-C
enclosure) (CAN/ULC-S303-M91)
Grade B & C Central Station Burglar Alarm Unit (UL1610) (CAN/ULC-S304-M88)
Home Health Care Signaling (UL1637)
When installing an NX-6 in compliance with Underwriters Laboratories, the following instructions must be observed:
! Initiating and indicating devices must be rated at 11.5 to 12.4 V DC residential, 12.0 V DC commercial.
! When using partitioning in Commercial Burglary applications, the main control must be protected by a 24-hour alarm circuit.
! Force Arming and Auto Arming shall not be enabled.
! For residential fire applications, the indicating devices shall be a Wheelock 34T-12 or equivalent.
! The "Listen-In" feature shall not be enabled.
! The Siren/Bell Test shall be enabled. The auxiliary outputs controlling the audible device require a minimum cutoff time of 15
minutes for commercial burglary, 4 minutes for residential applications, or 30 minutes for commercial burglary for Canada.
! For residential fire installations, the Dynamic Battery Test time cannot exceed four (4) hours.
! Ringback shall be enabled on UL commercial burglary installations.
! On commercial burglary installations, the fire initiating circuits shall not be connected.
! The Entry-Guard feature shall be disabled.
! Group Bypassing shall be disabled.
! Delay before dial seizure shall be set to “0”.
! Total current draw from aux power connections at terminal positions POS, AUX PWR, and SMOKE PWR must not exceed 400 mA.
! Remote Downloading shall not be used on UL listed systems.
! For residential burglary applications, the maximum entry and exit delay times shall be 45 and 60 seconds respectively. The exit
delay time shall not exceed 60 seconds for commercial burglar alarm applications.
! The keyswitch option shall not be used.
! The Telephone Line Monitor shall be enabled.
! The Telephone Line Cut delay shall not exceed 90 seconds.
! 24-hour communicator test transmission is required.
! For 24 hours of standby power using a 7.0 AH battery, limit auxiliary power load to 140 mA.
! For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
! The silent keypad option shall not be enabled.
! UL has only verified compatibility with the following listed DACRs and formats: Sure-Gard SG-MLR2-DG: 2,9,10,12,13,14; Silent
Knight 9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
! For burglary installations, cross-zoned detectors shall overlap 100 percent in the area of coverage and similar coverage areas must
be used. For example, interior protection is cross-zoned with interior protection, and so on.
! Expander trouble must activate the siren (Loc 37, Segment 2, LED 2)
! For UL 1637, expander trouble must activate keypad sounder (Loc 39, Segment 1, LED 8)
! The keypad used with wireless receivers and hardwire expansion must be able to display all zones in the system.
! For Canadian installations, the class II transformer secure tabs shall not be employed.
! The 4-wire smoke detector employed shall be rated to operate over the voltage range of 11.5 to 12.4V.
! Compatible listed devices: (Special Applications)
o Bell Output (Sirens): Wheelock models: NS-1215W, NS-121575W, NS4-1215W, NS4-121575W, AS-1215W, AS-121575W
o Horn / Strobe: System Sensor: S1224MC Strobe series; 1224MC Horn/Strobe series; H12/24 Horn series
o Smoke Output (4 wire detectors):
ESL: 500N series; 449CTE series; 521 series; 541 series
System Sensor models: 2112/24R; 2112/24TR; 2112/24AT; 2112/ATR; 2112/24AITR; 4WTA-B; 4WTR-B; 4WTAR-B;
4WITAR-B.
Detection Systems: F220-B6C; D273 series
Hochiki: SBC-4/12, 4/12W
MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS
(Residential Fire, Residential Burglary, Commercial Burglary)
! The NetworX NX-6 panel is necessary to initiate Residential and Commercial installations.
! At least one compatible keypad is needed for all applications.
! At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the AD10-12 bell and
Grade A bell housing shall be used.
! Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
! A minimum of two (2) keypads are required for Home Health applications and each keypad must be set to a unique address.
! The wireless devices are only UL listed for residential applications.
! The DACT shall be enabled for all commercial burglary applications.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NetworX NX-6 and is the answer not in the manual?

GE NetworX NX-6 Specifications

Operating Power IconOperating Power
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
Loop Specifications IconLoop Specifications
loop resistance for standard loop300 Ohms Maximum
loop resistance for 2-wire smokes30 Ohms Maximum
loop response500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
LED Keypad Specifications IconLED Keypad Specifications
led keypad current draw130 mA max.
led keypad dimensions width6.4"
led keypad dimensions height4.0"
led keypad dimensions depth1.1"
NX-148E LCD Keypad Specifications IconNX-148E LCD Keypad Specifications
nx-148e lcd keypad current draw110 mA max.
nx-148e lcd keypad dimensions width6.4"
nx-148e lcd keypad dimensions height5.3"
nx-148e lcd keypad dimensions depth1.0"
Enclosure and Shipping IconEnclosure and Shipping
metal enclosure dimension width11.25"
metal enclosure dimension height11.25"
metal enclosure dimension depth3.50"
shipping weight9 lbs.