NX-8 Control
14
Segment 2- Phone #1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8 to make
the designated number of attempts to Phone #2 before setting the "Fail To Communicate" condition and stop
reporting. Programming a "1" in this segment will cause the NX-8 to stop trying to communicate after the designated
number of attempts have been made to Phone #1. If a "2" is programmed in this segment, it will cause the NX-8 to
make the dial attempts in increments of two. The first two attempts will be made to Phone #1, the next two attempts to
Phone #2, then repeating until the total number of attempts designated in Segment 1 is completed.
COMMUNICATOR FORMAT SELECTIONS
DATA
FORMAT
DESCRIPTION
0
Local
Communicator is disabled
1
Universal 4+2
Two digit event code 1800hz transmit 2300hz handshake double round parity
40pps
2
3+1 fast (or 4+1)
One digit event code 1900Hz transmit 1400Hz handshake double round parity
20pps
3
Reserved
Reserved
4
Pager
2 digit event code DTMF transmission
5
3/1 or 4/1 slow
1800hz transmit 2300hz handshake double round parity 20 p.p.s. hex capability
6
3/1 or 4/1 slow
1800hz transmit 1400hz handshake double round parity 20 p.p.s. hex capability
7
3/1 or 4/1 fast
1800hz transmit 2300hz handshake double round parity 40 p.p.s. hex capability
8
3/1 or 4/1 fast
1800hz transmit 1400hz handshake double round parity 40 p.p.s. hex capability
9
3/1 or 4/1 fast with parity
1800hz transmit 2300hz handshake single round w/parity 40 p.p.s. hex capability
10
3/1 or 4/1 fast with parity
1800hz transmit 1400hz handshake single round w/parity 40 p.p.s. hex capability
11
4+2 express
2 digit event code DTMF transmission
12
4+2 fast
Two digit event code 1900hz transmit 1400hz handshake double round parity 20
p.p.s.
13
Ademco Contact ID
DTMF (see pages 52-53)
14
SIA
FSK (see pages 52-53)
15
Custom format
(See location 18, page 18)
REPORTING EVENTS TO PHONE NUMBER 1
Phone #1 has two programming locations that are used to select which events are reported to this phone number.
Location 4 is used to select which events are reported to Phone #1. Location 5 is used to select which partitions are
reported to Phone #1. If dual or split reporting is not desired, location 4 should be used to select all events to Phone
#1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and the split is based
on the event type (such as alarm, open/close, etc.), location 4 should be used to select only those events that should
be reported to Phone #1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired,
and the split is based on partition, location 4 should be programmed as a "0" and location 5 should be used to select
those partitions that should be reported to Phone #1. If no events should be reported to Phone #1, both locations
should be programmed as "0" (disabling all options).
LOCATION 4 - EVENTS REPORTED TO PHONE # 1 (2 segments, feature selection data)
Segment 1: 1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut , Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NX-1308E - Caddx 8 Zone LED Keypad and is the answer not in the manual?

GE NX-1308E - Caddx 8 Zone LED Keypad Specifications

Power IconPower
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E power supply12 VDC Regulated 2 AMPS
LED keypad current draw130 mA max.
LED keypad zones normal w/o sounder55 mA
NX-148E LCD keypad current draw110 mA max.
NX-148E LCD keypad w/o sounder75 mA
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Loop Specifications IconLoop Specifications
standard loop resistance300 Ohms Maximum
2-wire smokes resistance30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Weight and Dimensions IconWeight and Dimensions
LED keypad width6.4"
LED keypad height4.0"
LED keypad depth1.1"
NX-148E LCD keypad width6.4"
NX-148E LCD keypad height5.3"
NX-148E LCD keypad depth1.0"
metal enclosure width11.25"
metal enclosure height11.25"
metal enclosure depth3.50"
shipping weight9 lbs.