10 ADV20 QS, V1.02
Italiano English
Summary of Parameter Settings
a: The parameter can be set during operation.
Parameter Explanation Settings
Factory
Setting
NOTE
Group 0 User Parameters
00.00 Identity Code of the
AC motor drive
Read-only ##
00.01 Rated Current
Display of the AC
motor drive
Read-only #.#
00.02 Parameter Reset
0: Parameter can be read/written
1: All parameters are read only
8: Keypad lock
9: All parameters are reset to factory settings
(50Hz, 230V/400V or 220V/380V depends on
Pr.00.12)
10: All parameters are reset to factory
settings (60Hz, 220V/440V)
0
a00.03
Start-up Display
Selection
0: Display the frequency command value
(Fxxx)
1: Display the actual output frequency (Hxxx)
2: Display the content of user-defined unit
(Uxxx)
3: Multifunction display, see Pr.00.04
4: FWD/REV command
0
a00.04
Content of Multi-
function Display
0: Display the content of user-defined unit
(Uxxx)
1: Display the counter value (c)
2: Display the status of multi-function input
terminals (d)
3: Display DC-BUS voltage (u)
4: Display output voltage (E)
5: Display PID analog feedback signal value
(b) (%)
6: Output power factor angle (n)
7: Display output power (P)
8: Display PID setting and feedback signal
9: Display AVI (I) (V)
10: Display ACI (i) (mA)
11: Display the temperature of IGBT (h) (°C)
0
a00.05
User-Defined
Coefficient K
0. 1 to 160.0 1.0
00.06 Software Version Read-only #.##
00.07 Reserved
00.08 Password Input 0 to 9999 0
00.09 Password Set 0 to 9999 0
00.10 Reserved
00.11 Reserved
00.12
50Hz Base Voltage
Selection
0: 230V/400V
1: 220V/380V
0
00.13
User-defined Value 1
(correspond to max.
frequency)
0 to 9999
0