ADV20 QS, V1.02 17
Italiano English
Parameter Explanation Settings
Factory
Setting
NOTE
a05.12 13th Step Speed
Frequency
0.00 to 600.0 Hz 0.00
a05.13 14th Step Speed
Frequency
0.00 to 600.0 Hz 0.00
a05.14 15th Step Speed
Frequency
0.00 to 600.0 Hz 0.00
Group 6 Protection Parameters
390.0V
780.0V
06.00
Over-Voltage Stall
Prevention
115/230V series: 330.0V to 410.0V
460V series: 660.0V to 820.0V
0.0: Disable over-voltage stall prevention
06.01
Over-Current Stall
Prevention during
Accel
0:Disable
20 to 250%
170
06.02
Over-Current Stall
Prevention during
Operation
0:Disable
20 to 250%
170
06.03
Over-Torque
Detection Mode
(OL2)
0: Disabled
1: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL1 or OL occurs.
2: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
3: Enabled during accel. After the over-
torque is detected, keep running until OL1 or
OL occurs.
4: Enabled during accel. After the over-
torque is detected, stop running.
0
a06.04
Over-Torque
Detection Level
10 to 200% 150
06.05
Over-Torque
Detection Time
0.1 to 60.0 sec 0.1
06.06
Electronic Thermal
Overload Relay
Selection
0: Standard motor (self cooled by fan)
1: Special motor (forced external cooling)
2: Disabled
2
06.07
Electronic Thermal
Characteristic
30 to 600 sec 60
06.08
Present Fault
Record
06.09
Second Most
Recent Fault Record
0: No fault
1: Over current (oc)
2: Over voltage (ov)
3: IGBT Overheat (oH1)
4: Reserved
5: Overload (oL)
6: Overload1 (oL1)
7: Motor over load (oL2)
8: External fault (EF)
9: Current exceeds 2 times rated current
during accel.(ocA)
10: Current exceeds 2 times rated current
during decel.(ocd)
11: Current exceeds 2 times rated current
0