18 ADV20 QS, V1.02
Italiano English
Parameter Explanation Settings
Factory
Setting
NOTE
06.10
Third Most Recent
Fault Record
06.11 Fourth Most Recent
Fault Record
06.12
Fifth Most Recent
Fault Record
during steady state operation (ocn)
12: Ground fault (GFF)
13: Reserved
14: Phase-Loss (PHL)
15: Reserved
16: Auto Acel/Decel failure (CFA)
17: SW/Password protection (codE)
18: Power Board CPU WRITE failure (cF1.0)
19: Power Board CPU READ failure (cF2.0)
20: CC, OC Hardware protection failure
(HPF1)
21: OV Hardware protection failure (HPF2)
22: GFF Hardware protection failure (HPF3)
23: OC Hardware protection failure (HPF4)
24: U-phase error (cF3.0)
25: V-phase error (cF3.1)
26: W-phase error (cF3.2)
27: DCBUS error (cF3.3)
28: IGBT Overheat (cF3.4)
29: Reserved
30: Reserved
31: Reserved
32: ACI signal error (AErr)
33: Reserved
34: Motor PTC overheat protection (PtC1)
35-40: Reserved
Group 7 Motor Parameters
a07.00
Motor Rated Current 30 %FLA to 120% FLA FLA
a07.01
Motor No-Load
Current
0%FLA to 99% FLA 0.4*FLA
a07.02
Torque
Compensation
0.0 to 10.0 0.0
a07.03 Slip Compensation
(Used without PG)
0.00 to 10.00 0.00
07.04
|
07.09
Reserved
07.10
Accumulative Motor
Operation Time
(Min.)
0 to 1439 Min. 0
07.11
Accumulative Motor
Operation Time
(Day)
0 to 65535 Day 0
07.12
Motor PTC
Overheat Protection
0: Disable
1: Enable
0
07.13
Input Debouncing
Time of the PTC
Protection
0~9999(*2ms) 100
07.14
Motor PTC
Overheat Protection
Level
0.1~10.0V 2.4