ADV20 QS, V1.02 11
Italiano English
Parameter Explanation Settings
Factory
Setting
NOTE
00.14
Position of Decimal
Point of User-
defined Value 1
0 to 3
0
Group 1 Basic Parameters
01.00
Maximum Output
Frequency (Fmax)
50.00 to 600.0 Hz 60.00
01.01
Maximum Voltage
Frequency (Fbase)
0.10 to 600.0 Hz 60.00
01.02
Maximum Output
Voltage (Vmax)
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
220.0
440.0
01.03
Mid-Point Frequency
(Fmid)
0.10 to 600.0 Hz 1.50
01.04
Mid-Point Voltage
(Vmid)
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
10.0
20.0
01.05
Minimum Output
Frequency (Fmin)
0.10 to 600.0 Hz 1.50
01.06
Minimum Output
Voltage (Vmin)
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
10.0
20.0
01.07
Output Frequency
Upper Limit
0.1 to 120.0%
110.0
01.08
Output Frequency
Lower Limit
0.0 to100.0 %
0.0
a01.09
Accel Time 1 0.1 to 600.0 / 0.01 to 600.0 sec 10.0
a01.10
Decel Time 1 0.1 to 600.0 / 0.01 to 600.0 sec 10.0
a01.11
Accel Time 2 0.1 to 600.0 / 0.01 to 600.0 sec 10.0
a01.12
Decel Time 2 0.1 to 600.0 / 0.01 to 600.0 sec 10.0
a01.13
Jog Acceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
a01.14
Jog Deceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
a01.15
Jog Frequency 0.10 Hz to Fmax (Pr.01.00) Hz 6.00
01.16
Auto acceleration /
deceleration (refer
to Accel/Decel time
setting)
0: Linear Accel/Decel
1: Auto Accel, Linear Decel
2: Linear Accel, Auto Decel
3: Auto Accel/Decel (Set by load)
4: Auto Accel/Decel (set by Accel/Decel
Time setting)
0
01.17
Acceleration S-
Curve
0.0 to 10.0 / 0.00 to 10.00 sec 0.0
01.18
Deceleration S-
Curve
0.0 to 10.0 / 0.00 to 10.00 sec 0.0
01.19
Accel/Decel Time
Unit
0: Unit: 0.1 sec
1: Unit: 0.01 sec
0
Group 2 Operation Method Parameters
a02.00
Source of First
Master Frequency
Command
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI
3: RS-485 (RJ-45) communication
4: Digital keypad potentiometer
1