22
80415F_MSW_GFX4-IR_05-2019_ENG
ADVANCED SETTINGS
Input lter
FUNCTIONAL DIAGRAM
604
FLt.2
R/W
Digital filter for auxiliary input
0.0 ... 20.0 sec
0.1
Sets a low pass lter on the auxiliary input, running the average of values read in the
specied time interval. If = 0 , excludes the average lter on sampled values.
Auxiliary
input
Select sensor
(AI.2)
Scale limits, decimal
point, Offset (H.S2,
L.S2, dP.2, oFS.2)
Low pass f
ilter
(Flt.2)
Internal In.2
See generic
alarms and
Control
602
In.2
R
Value of auxiliary input
606
Er.2
R
Error code for self-diagnosis
of auxiliary input
0 No error
1 Lo (value of process variable is < Lo.S)
2 Hi (value of process variable is > Hi.S)
3 ERR [third wire interrupted for PT100 or input values below minimum
limits (ex.: for TC with connection error)]
4 SBR (probe interrupted or input values beyond maximum limits)
Error code table
Read state