INPUTS
MAIN INPUT
The modular power controller has 4 main inputs to control 4 temperature zones, to which you can connect temperature
sensors (thermocouples and RTD), linear sensors or custom sensors to acquire process variable (PV) values.
To congure, you always have to dene the type of probe or sensor (tYP), the maximum and minimum scale limit (Hi.
S – Lo.S) for the process variable value, and the position of the decimal point (dP.S).
If the sensor is a thermocouple or resistance thermometer, the minimum and maximum limits can be dened on the specic
scale of the sensor. These limits dene the width of the proportional control band and the range of values settable for the
setpoint and alarm setpoints.
There is a parameter to correct the offset of the input signal (oF.S): the set value is algebraically added to the read of
the process variable.
You can read the state of the main input (Err) in which an input error is reported: when the process variable goes beyond
the upper or lower scale limit, it assumes the value of the limit and the corresponding state reports the error condition:
Lo = process variable < minimum scale limit
Hi = process variable > maximum scale limit
Err = Pt100 in short circuit and input value below minimum limit,
4...20mA transmitter interrupted or not powered
Sbr = Tc probe interrupted or input value above maximum limit
If noise on the main input causes instability of the acquired value, you can reduce its effect by setting a low pass
digital lter (Flt). The default setting of 0.1sec is usually sufcient.
You can also use a digital lter (Fld) to increase the apparent stability of the process variable PV; the lter introduces
a hysteresis on its value: if the input variation remains within the set value, the DPV value is considered unchanged.