EasyManuals Logo
Home>Glow-worm>Boiler>ULTIMATE 30c

Glow-worm ULTIMATE 30c User Manual

Glow-worm ULTIMATE 30c
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
0020167175_01 - 02/13 - Glow-worm
11 Commissioning
i
IMPORTANT:
At the time of commissioning, complete all relevant
sections of the Benchmark Checklist located in the centre
pages of this document.
The commissioning should be carried out by a competent person
approved at the time by the Health and Safety Executive and in
accordance with the current issue of BS6798.
11.1 Reading the lling pressure
The boiler is equipped with an analogue pressure gauge.
The pressure guage is located behind the front panel of the
boiler on the ow pipe. The guage is intended to be used as an
installation aid, the guage is not intended to be used by the
customer.
2
1
3
Key
1 White area, pressure too low
2 Grey area, normal operating pressure
3 Red area, pressure too high
To ensure the correct operation of the heating installation, the
indicator on the pressure gauge should be within the grey area
(2) in approximately the central position as shown in the diagram.
This corresponds to a lling pressure of between 0.1 MPa and 0.2
MPa (1.0 bar and 2.0 bar).
11.2 Switching on
Do not operate the boiler without water.
Make sure that the system has been thoroughly ushed out with
cold water and that all cleanser if used has been removed.
With the gas service isolation valve closed, with no demand
from any external controls and the power supply to the boiler
switched o .
Test for gas tightness and purge air from the gas supply.
Switch on the power supply to the appliance.
Make sure that the domestic hot water and heating functions
on your appliance are not activated.
11.3 Filling the CH system (Central heating)
Make sure that the installation's cold water inlet isolating valve is
open.
Open the isolating valves located on the connections: they must
be positioned in the direction of the ow.
3
2
1
Key
1 Air vent
2 Pump
3 Screw for the pump shaft
Open the plug on the air vent located on the pump and
automatic air vents on the installation.
If the (CH.) pressure falls below 0.4 bar, the display will ash the
current pressure and the boiler will not operate. To increase the
pressure, the CH circuit requires " Topping up".
i
IMPORTANT:
When turning the 230Vac supply on to the boiler should
the water pressure be less than 0.5 bar an automatic air
vent function will be activated for a period of 5 minutes.
During this time the pressure should be increased and
air vented from the system. Note that the burner will not
re in either the CH or DHW mode and the display will
blink displaying the current water pressure.
Vent air from each radiator until the water ows normally, then
close the vents.
Leave the pump's air vent open.
i
IMPORTANT:
The following two operations will unblock the pump's
engine after a prolonged storage period and will purge
the air from the pumps circuit.
Remove the screw from the pump shaft and introduce a at
screwdriver. A trickle of water, under no pressure should
normally come out of the pump.
Rotate the pump's shaft through several turns, then replace
the screw.
INSTALLATION
- 21 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Glow-worm ULTIMATE 30c and is the answer not in the manual?

Glow-worm ULTIMATE 30c Specifications

General IconGeneral
BrandGlow-worm
ModelULTIMATE 30c
CategoryBoiler
LanguageEnglish

Related product manuals