3.6.5 AC CONDUCTOR WIRING
Make sure the IC Series is fully disconnected from the battery bank and no AC power is connected to the
Inverter/Charger before commencing any AC wiring connections.
ACINPUTSWIRING(50ADualIN,DualOutConguration)
• Remove the AC cover plate.
• Route the wires: IN1 (Hot1), IN2 (Hot2), ACN-IN (neutral), and Ground from the main panel through the AC Input
strain relief clamp. Tighten the strain relief clamp securely on the wires. Always leave a little extra slack in the wiring.
•
Connect the HOT1 wire (black) from the main panel to the Inverter/Chargers IN1 terminal. Connect the HOT2
wire (red) from the main panel to the Inverter/Charger’s IN2 terminal. Tighten the terminals securely. Note: To
use the Battery Charger, IN1 must always be connected to an AC Input.
•
Connect the NEUTRAL (white) from the main panel to the Inverter/Chargers ACN-IN terminal. Tighten the terminal
securely.
AC OUTPUTS WIRING
•
Route the wires (hot, neutral, and ground) from the sub panel through the AC INV. Output strain relief clamp.
Tighten the strain relief clamp securely on the wires. Always leave a little extra slack in the wiring.
• Connect the OUT1 wire (black) and OUT2 (red) from the Inverter/Charger to the sub panel. Tighten the terminals
securely.
•
Connect the ACN-OUT Neutral out (white) from the Inverter/Charger to the sub panel. Tighten the terminal securely.
• To prevent possible damage to the case, always add additional external non-conductive strain relief when using
large diameter multi-conductor cables for AC inputs and AC outputs.
INSTALLATION