User Manual V1.6-2022-01-05 03 OTHERS
ERROR
MESSAGE
EXPLANATION REASON SOLUTIONS
DC Bus High BUS voltage is
over-high
/ Try to restart the inverter. Check
if the fault still occurs. If not, it
means it is caused by an occasional
situation,or contact after-sales.
Back-Up Over
Load
Back-up side is
over loaded
Total back-up load
power is higher
than the back-up
nominal output
power
Decrease back-up loads to make
sure the total load power is lower
than back-up nominal output power
(please refer to page 24).
AC HCT
Check Failure
The inverter's AC
HCT check failure.
Inverter hardware
current sensor
failure.
Try to restart the inverter. Check
if the fault still occurs. If not, it
means it is caused by an occasional
situation,or contact after-sales.
GFCI Device
Check Failure
GFCI Device
Check Failure
GFCI device failure Try to restart the inverter. Check
if the fault still occurs. If not, it
means it is caused by an occasional
situation,or contact after-sales.
3.2 Troubleshooting
Checking As Start A-ES Up And Turn On AC Power
Battery settings, BMS communication and safety country:
After connecting Solar-WiFi* (*The Wi-Fi signal is named
the last 8 characters of the inverter's serial No.), check on PV
Master App "Param" to make sure battery type is the same as
what you have installed, and "Safety Country " Setting is right.
Please set it right in "Set" if the setting is not right.
Note: For compatible lithium batteries, BMS status will display
"Normal" after selecting the right battery company.
Functional Safety: The software version is displayed on PV
Master App "Param"→"Firmware Version".
Param
Battery (Battery-Box H 11.5)
Battery Status
Battery Data
BMS Status
SOH (From BMS)
Protocol Code
Charge Current Limit (From BMS)
Discharge Current Limit (From BMS)
Waring (From BMS)
Temperature (From BMS)
Overview Param Set
Inverter
SN
Firmware Version
Safety Country
Work Status
Error
93648ENU172W0003
02024
Brazil
Normal (Back-Up)
Problems During Operation
A-ES does not start up with battery only
Solution:
Make sure the voltage of battery is higher than 100V, otherwise battery cannot start A-ES up.
A-ES not started up with PV only
Solution:
1. Make sure the voltage of PV is highter than 100V (need 200V to enter on-grid mode).
2. Make sure the connection between A-ES and PV panels: polarities are (+/-) not reversed.