16
Remarks:SpecificationsofACcablesshouldbetypeofH05VV‐Forsimilar.
3.4.2 DCSideConnection
A Make sure the maximum open circuit voltage (Voc) of each PV string
doesnotexceedtheinv erterinputvoltageVmaxunderanycondition.
B UsePhoenixorMulti‐contactconnectorsforPVarrayterminals.
C Connect the positive and negative terminals of the PV panel to
corresponding terminals on the Inverter. The DC terminal on each Inverter
canbear20ADCcurrent.
PhoenixCont actConnectors
Malesideconnector(PV+)Femalesideconnector(PV‐)
Bothtypesofconnectorsmustbeequippedinpairstrictlyaccordingtoabove
graphs.
1. InsertthestrippedPVconductor.