MULTI VRF- INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
92
3.8.4 Selection of air switch and power cord
Model
Power Cord Size
Air Switch
apacity
(A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power
Cord
(mm
2
/AWG)
GMV-ND28ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND36ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND50ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND63ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND71ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND90ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND112ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND125ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND140ZD/A-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
3.9 Installation of Fresh air Processing unit
3.9.1 Outline and installation dimension

Table of Contents

Other manuals for Gree GMV-ND22PLS/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND22PLS/A-T and is the answer not in the manual?

Gree GMV-ND22PLS/A-T Specifications

General IconGeneral
BrandGree
ModelGMV-ND22PLS/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals