GMV5 Home DC Inverter Multi VRF Units
265
4. Troubleshooting
4.1 Analysis in Forms
4.1.1 Control
Fault
code
Fault
Possible causes
Solution
F0
Faults in the ODU’s
main board (such as
memory and
address chip
exceptions)
1 The clock chip on
the main board is
damaged.
2 The memory chip
on the main board
is damaged.
3 The address chip
on the main board
is damaged.
1 Replace the small CPU board
2 Replace the control board.
3 Replace the control board.
FC
Faults in the
constant frequency
compressors current
sensor
1 The constant
frequency
compressor is not
started.
2 The current
detection bord is
faulty.
3 The main boards
detection circuit is
faulty.
1 If the compressor is not started, check if the AC contact is
closed. If not, replace the AC contact.
If the connection is loose, reconnect it;
2 Replace the current detection board.
3 Replace the main board.
U2
Wrong outdoor
capacity code setting
1 The capacity code
is wrong.
2 The dial
component is faulty.
1 Modify the capacity code setting.
2 Replace the main board.
U3
Power phase
sequency protection
1 The three phase
power cable is not
connected correctly.
2 The main boards
detection circuit is
faulty.
1 Check connection of the power cable.
2 Replace the control board.
UL
Wrong emergency
operation dial code
1 The dial setting is
wrong.
2 The dial
component is faulty.
1 Modify the dial setting.
2 Replace the main board.
C0
1. The
If C0 is not displayed on the control board of the ODU,

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree SXVD200LCJ2/A-K and is the answer not in the manual?

Gree SXVD200LCJ2/A-K Specifications

General IconGeneral
BrandGree
ModelSXVD200LCJ2/A-K
CategoryInverter
LanguageEnglish

Related product manuals