GMV5 Home DC Inverter Multi VRF Units
380
Usage of Converter Configuring Software:
When the converter is working, hold the button "SET‖ for 5 seconds. Function LED will be
flickering, indicating that the converter has entered the baud rate setting mode. Then you can use
the converter configuring software to set the baud rate of converter. Baud rate is supported by the
converter (baud rate of air conditioner’s communication interface matches with the baud rate of
USB interface automatically):
Ex-factory defaulted baud rate: (unit: bps)
Baud rate of AC interface
Baud rate of USB interface
Baud rate look-up table for RS485 interface (unit: bps)
Baud rate look-up table for HBS interface (unit: bps)
Baud rate look-up table for CAN interface (unit: bps)