Description Factory settings Own settings
Start ↔ stop delay 2 s
After-run delay 2 s
After-run delay, high level 2 s
Analog level sensor
AI1 (CU 362)
Level, pressure
4-20 mA
Min. value: 0 m
Max. value: 5 m
10.3 Level
Description Factory settings Own settings
Overflow level 4.95 m
High level 4.75 m
Alarm level 3.5 m
Start level 2 2.0 m
Start level 1 1.75 m
Stop level 1 0.5 m
Stop level 2 0.5 m
Dry-running level 0.25 m
Foam-draining level 0.15 m
10.4 CU 362 configuration
Description Factory settings Own settings
Units and frequency SI
Password, Operation menu Disabled
Password, Settings menu Disabled
Display language English
10.5 SMS configuration
Description Factory settings Own settings
SMS phone number 1 +45 12345678
SMS phone number 2 +45 12345678
SMS phone number 3 +45 12345678
Send alarm SMS to Primary SMS number
Acknowledgement deadline 10 minutes
SMS heartbeat message Monday to Sunday at 12:30
SMS authentication, method Via PIN code
SMS authentication, PIN code 1234
10.6 SCADA configuration
Description Factory settings Own settings
SCADA callback Disabled
SCADA phone number +45 12345678
Number of retries 3
Incoming calls, PIN code enabled Disabled
Incoming calls, PIN code 1234
10.7 System alarms
Description Factory settings Own settings
Overflow -
High level -
Alarm level -
Dry running -