5
/
10
OPTIONAL SETTING AND INPUT/OUTPUT SETTING OF INDOOR UNIT
5.3.
CHANGING OF OPTIONAL FUNCTIONS AND SETTING CONDITIONS
5.3.1. OPTIONAL SETTING ITEMS
Optional Setting Items
(A)
Code
Items
Individual
Setting
Availability
(B) Setting
Conditions
b1
Cancel of Adjusting Set
Temperature for Heating
Operation
A
00: Standard
01: Cancel
b2
Circulator for Heating
Operation
A
00: Standard
01: Function
b3
3 Minutes Compressor OFF
Guard
A
00: Standard
01: Function
b4 Period for Filter Sign A
00∼04 *1)
b5 Fixing Operation Mode N
00: Standard
01: Fixed
b6 Fixing Setting Temperature N
00: Standard
01: Fixed
b7 Fixing Cooling Operation N
00: Standard
01: Fixed
b8
Automatic Cooling/Heating
Operation
N
00: Not Available
01: Available
b9 Fixing Fan Speed N
00: Standard
01: Fixed
C1 Not Prepared ― Not Used
C2 Not Prepared ― Not Used
C3 Not Prepared ― Not Used
C4
Drain Pump Operation in
Heating
A
00: Not Available
01: Available
C5 Increasing Fan Speed A Not Used
C6
Increasing Fan Speed When
Thermo-OFF in Heating
A
00: Not Available
01: Available
*1),00: Standard, 01: 100Hours, 02: 1200Hours, 03: 2500Hours, 04: No Indication
Optional Setting Mode (Mode Number “01”)
Select the item code
by pressing the “TIME”
or switch.
Item Code of Optional
Setting
<Example>
When selecting C5
(increasing Fan Speed)
COOL
SERVIC