Planning Excel 800
EN1B-0375GE51 R0910
14
C-Bus Cables
Note
Observe national regulations for C-Bus cables!
For Europe, only shielded cable is permitted.
For the U.S., shielded or unshielded cable can be used.
Cable type Description Recommended for
J-Y-(ST)Y
2 x 2 x 0.8
shielded,
twisted pair
Europe, inside cabinet
A-Y-(ST)Y
2 x 2 x 0.8
shielded,
twisted pair
Europe, outside cabinet
AK 3702
unshielded,
twisted pair
US
not approved for Europe
AK 3740A shielded
US (low-cost)
not approved for Europe
Belden 9842 twisted pair Europe, US also possible
Belden 9841 shielded US
AK 3702
unshielded,
twisted pair
US
not approved for Europe
AK 3740A shielded
US (low-cost)
not approved for Europe
Table 21 C-Bus cable types
Maximum Cable Length
The maximum C-Bus cable length is 1200 m (4000 ft).
See section "C-Bus Topologies" on page 11.