Power Supply Calculations
134 MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
7.3 Calculating the System Current Draw
7.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7-3 on page 135. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7-3 on page 135. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7-3 on page
135.
When calculating current draw and the battery size, note the following:
‘Primary’ refers to the main power source for the control panel
‘Secondary’ refers to the control panel’s backup batteries
All currents are given in amperes (A). Table 7-2 shows how to convert milliamperes and
microamperes to full amperes.
7.3.2 How to Use Table 7-3 on page 135 to Calculate System Current Draw
Use Table 7-3 on page 135 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Device Compatibility Document for
compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 7-4 on page 136
Following are the types of current that can be entered into Table 7-3 on page 135:
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire
alarm condition during a loss of AC power.
TABLE 7-2:Converting to Full Amperes
To convert... Multiply Example
Milliamperes (mA) to
amperes (A)
mA x 0.001 3 mA x 0.001 = 0.003A
Microamperes (
µA) to
amperes (A)
µA x 0.000001 300 µA x 0.000001 = 0.0003 A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell MS-5UD Series and is the answer not in the manual?

Honeywell MS-5UD Series Specifications

General IconGeneral
BrandHoneywell
ModelMS-5UD Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals