Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 25
Programming Programming
Table 3.2 lists and describes MN control module and panel bell circuit Type IDs.
Table 3.2 MN Control Type IDs
Activations will generate mass notification events locally and over a network. Trouble conditions at these points will generate MN trou-
bles.
3.3.6 Special Function Zones
The MN Special Function Zones in Table 3.3 below activate when an MN alarm, supervisory, or trouble event occurs.
Table 3.3 MN Special Function Zones
The MN Special Function Zones are available as indicated in Table 3.4.
Table 3.4 MN Special Function Zone Availability
3.3.7 MN Active Tone
When MN has the highest priority in a network and the DVC is operating in Mass Notification mode, it must be programmed in VeriFire
Tools to generate an “MN Active Tone”. This programming is required for two reasons:
It generates an audible reminder every 30 seconds that MN has control of the system and that fire signals may be suppressed if MN
is the highest priority.
Type Code
Point
Type
Point Characteristics
Silenceable
Switch
Inhibit
Walk
Test
Device Function
MNS
GENERAL
NAC N N N Mass notification supervised output.
MNS
CONTROL
NAC N N N Mass notification supervised NAC.
MNS
STROBE
NAC N N N Mass notification supervised NAC.
MNS
SPEAKER
NAC N N N Mass notification supervised NAC for speaker
circuits.
MNS RELAY Relay N N N Mass notification relay output.
NOTE: Use ZF20 in the map of an LED annunciator programmed with a “monitor” mode as a dedicated MN alarm indicator.
Special
Function
Code
Name Description
ZF20 MN Alarm Zone Activates for local events and network ZF20 activations when an MN alarm is present in the system. It
suppresses fire protection when MN is prioritized as higher than fire (see “Output Event Suppression” on
page 40). It is sent out to the network, and each networked panel will check the ZF20’s source against its
table of mapped MN nodes. If the source has a match in the table, fire protection will be suppressed in the
panel that made the match. Logic equations will be activated.
ZF21 MN Supervisory
Zone
Activates for local events when there is an MN supervisory in the system.
ZF22 MN Trouble
Zone
Activates for local events when an MN trouble occurs.
ZF20 ZF21 ZF22
NFS2-3030

NCA-2
NFS2-640/NFS-320/SYS

DVC
ONYXWorks Workstation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier DVC and is the answer not in the manual?

Honeywell Notifier DVC Specifications

General IconGeneral
BrandHoneywell
ModelNotifier DVC
CategorySecurity System
LanguageEnglish

Related product manuals