Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 7
Mass Notification Features Introduction
1.2 Mass Notification Features
MN events can be programmed as higher or lower than fire events, based on risk analysis.
MN alarms suppress fire alarm events when MN is the highest priority.
MN alarms are generated locally
by an ACU, LOC, or CCS page.
by manual activation of a UL-approved switch or button device installed for initiating MN alarms. A Listed UL2017 initiating
switch/device is required.
MN events generate messages over Noti•Fire•Net to MN-mapped nodes.
Programmable using VeriFire Tools.
Automatic activation of Special Function Zone ZF20 to signal MN alarm.
Figure 1.1 Block Diagram Example of an MN System
LOC
(DVC-RPU and
LCD-160)
NFS2-640
NFS-320/SYS
ACU
(NFS2-3030 and
DVC)
CCS
(NCA-2 and DVC,
or ONYXWorks)
NCA-2
LOC
(NCA-2 or NFS2-
3030 and DVC)
ACU
(NCA-2 and
DVC)
LOC
(DVC-RPU and
LCD-160)
LOC
(DVC-RPU and
LCD-160)
LOC
(DVC-RPU and
LCD-160)
LOC
(DVC-RPU and
LCD-160)
Noti•Fire•Net
Notes:
MN System works on Standard and Hi-speed Noti•Fire•Net
A total of 15 ONYXWorks workstations may participate in paging on a mass notification system.

Questions and Answers: